Intelligent Protection Classification of Transients in Two-Core Symmetric Phase Angle Regulating Transformers
This paper investigates the applicability of time and time-frequency features based classifiers to distinguish internal faults and other transients - magnetizing inrush, sympathetic inrush, external faults with current transformer saturation, and overexcitation - for Indirect Symmetrical Phase Angle Regulating Transformers (ISPAR). Then the faulty transformer unit (series/exciting) of the ISPAR is located, or else the transient disturbance is identified. An event detector detects variation in differential currents and registers one-cycle of 3-phase post transient samples which are used to extract the time and time-frequency features for training seven classifiers. Three different sets of features - wavelet coefficients, time-domain features, and combination of time and wavelet energy - obtained from exhaustive search using Decision Tree, random forest feature selection, and maximum Relevance Minimum Redundancy are used. The internal fault is detected with a balanced accuracy of 99.9 no-fault transients are classified with balanced accuracy of 99.5 show potential for accurate internal fault detection and localization, and transient identification. The proposed scheme can supervise the operation of existing microprocessor-based differential relays resulting in higher stability and dependability. The ISPAR is modeled and the transients are simulated in PSCAD/EMTDC by varying several parameters.
READ FULL TEXT